thnks for your guideline engr jawad... as i have seen personally these two capacitors of 25kva and one of 15kva are installed parallel, as i switch of these capacitors due to running inductive load power factor comes to 0.75 and as i switch one this capacitor bank it turn to 0.92. along with...
as attached files...the one with the calculation using above formulas, resulting the 75uF Capacitor which is too low value for such load. where as on the site there are two capacitors of 234uF and one 100uf are installed in parallel...as attached files...do help me out in this regard
i have already gone through this calculation but couldn't found a better result... ill show my working by uploading the pics... Mr. Baluncore this is the real situation in the industry where i am working. as it is 3 phase 400V, and we are having 1500KVA transformer as well and on HT Panel max...
Hello... kindly help me out in designing of power capacitor to improve the power factor as the given load is 950 KWatt and power factor is 0.7, as i want to improve the power factor to 0.92 then what formula i should use to design the capacitor as the Voltage line to line are 400Volts